Power Cable and Accessory
Home > Products > Power Cable and Accessory > Details
Product Center
Product inquiry
Please enter the name of the product to query

+86-0431-84158222

+86-0431-84155885

Cold shrinkable cross-linked cable accessory
Power Cable and Accessory
64KV/100KV full cold shrinkable cross-linked cable accessories is formed as a whole. Its unique umbrella structure is reasonable.

64KV/100KV full cold shrinkable cross-linked cable accessories is formed as a whole. Its unique umbrella structure is reasonable. Anti-pollution small and large umbrella is sued for external insulation structure, applicable for IV level heavily polluted area. Unique stress cone realize even field intensity on special surface and low operation field strength, ensuring long-term safe operation of the terminal. Terminal rubber prefabricated part <1PC both end dual metal structure ensure reliable shielding and sealing. A special earth ring is designed for metal sleeve cable and the cable terminal is reliably grounded and it is easy to disassemble the ground wire. This product has a wide scope of application and is easy to install.




Each performance index of the product reaches or exceeds requirements in GB11017-2002 and IEC60840-1999.

 

S/N

Item

Standards

This product 

1

Ambient temperature partial discharge test

96kV,≤5PC

96kV,≤3pC

2

High temperature partial discharge test

96kV,≤5PC

96kV,≤3pC

3

Impulse voltage test

±550kV, 10 times

±550kV, 10 times

4

Power frequency voltage test

160kV,15min

160kV,15min/230kV,1min

5

Rainfall withstand voltage test

185kV,1min

185kV,1min

6

Radio interference test

81kV,≤450μV

81kV,≤300μV


Technical requirements:
 
1. Rated voltage: 64/110kV.
 
2. Cross-section of cable: Otherwise designed for 240mm2-1000mm2、1000mm2 and above.
 
3. Rated insulation level: 126/230/550kV.
 
Use conditions:
 
1. Ambient temperature: -50℃~+50℃.
 
2. Operating temperature: Conductor temperature at normal operation: ≤90℃.
 
3. Conductor temperature when short-circuit: ≤250℃.
 
Electrical test:
 
Each performance index of the product reaches or exceeds requirements in GB11017-2002 and IEC60840-1999.