+86-0431-84158222
+86-0431-84155885
As global warming becomes increasingly prominent, the environmental awareness of people also increases. Medium voltage switch devices have been increasingly used in the grid distribution system by lots of middle voltage users.They are also the essential products of Strong Smart Grid, which relate directly to the safe and reliable operation of the grid. While the economy is developing sustainably and cities are expanding, medium voltage gas insulated switchgears (GIS), with merits such as small volume, free of maintenance, high reliability under harsh climates and notable economic benefits, have developed prosperously since 1990s, and the demand is also growing. However, the SF6 gas used in the middle voltage GISs is one of the six kinds contributing to the greenhouse effect, and is widely questioned. Therefore, scale production of GISs without / with less SF6 will increase the economy and provide excellent stability of performance and a structure of light weight simultaneously. It is an irreversible trend for metal-enclosed switchgears without / with less SF6 gas to take place of air-insulated and SF6 gas-insulated metal-enclosed switchgears.
S/N |
Item |
Unit |
Parameter |
||
1 |
Rated voltage |
kV |
12 |
||
2 |
Rated current |
A |
630/1250 |
||
3 |
Rated insulation level |
1min power frequency withstand voltage |
Phase to phase and phase to ground |
kV |
42 |
Fractures |
kV |
48 |
|||
Lightning impulse withstand voltage (peak) |
Phase to phase and phase to ground |
kV |
75 |
||
Fractures |
kV |
85 |
|||
4 |
Circuit breaker |
Rated short-circuit open current |
kA |
20/25 |
|
Rated short-circuit closing current (peak) |
kA |
50/63 |
|||
Rated short-time withstand current (4 s) |
kA |
20/25 |
|||
Rated peak withstand current |
kA |
50/63 |
|||
Rated operation sequence |
— |
O-0.3s-CO-180s-CO |
|||
Mechanical life |
Circuit breaker |
Times |
10000 |
||
Three-position disconnector and grounding switch |
Times |
5000 |
|||
5 |
Load-break switch |
Rated short-time withstand current |
kA |
20 |
|
Rated peak withstand current |
kA |
50 |
|||
Mechanical life |
Load-break switch |
Times |
10000 |
||
Three-position disconnector and grounding switch |
Times |
5000 |
|||
Load switch opening and closing cycle level |
Level |
E3 |
|||
6 |
Rated inflation pressure of gas tank (gage pressure at 20℃)(filled with dry air) |
MPa |
0 |
||
7 |
IP grade of gas tank |
— |
IP67 |
||
8 |
IP grade of cabinet |
— |
IP4X |
||
9 |
Annual leak rate |
— |
≤0.05% |
1. Employs vacuum arc extinction technology and uses environmentally friendly dry air as the major insulating medium instead of SF6 gas;
2.The cabinet is designed to be fully enclosed and insulated without any
exposed live parts and can therefore operate in severe environment for a long
time;
3. The gas tank is designed to be zero gauge pressure with a protection grade
of IP 67. The occurrence of leaks is reduced to almost none to significantly
prevent the possibility of invasion of dust and damp;
4. The gas tank is designed to be zero gauge pressure, therefore it can run
safely under zero gauge pressure and fulfill all related test standards.
5. An explosion-proof membrane is provided to the bottom of gas tank. In the
case that the pressure increases due to internal faults, the membrane will
explode to release the pressure and the gas will be discharged to the back to
avoid damaging operators in front of the cabinet;
6. By upper isolation, it is able to be
grounded and closed with the arc extinguishing chamber, thus ensuring the
safety and reliability.
7. The three phases at the disconnector fracture are independent and visible.
Contactor positions are directly visible and provided with LED lighting;
8. The switch cabinet has passed the internal arcing
test, IAC-AFL/20KA, 1S;
9. The structure is designed as standardized and modularized for the extension of
circuits, exchange of units and alteration of plan;
10. The functions are completed by fundamental function units such as load
switches and circuit breakers and typical function units such as enhancement
cabinet, contact cabinet, PT cabinet and measure cabinet;
11. Fully modularization is fulfilled by plug-in type extension busbar through
arbitrary combinations;
12. Small volume and small occupied area with the minimum volume for a single
device to be: 450*905*1500 (mm).