+86-0431-84158222
+86-0431-84155885
S/N |
Item |
Unit |
parameters |
||||
1 |
Rated voltage |
kV |
40.5 |
||||
2 |
Rated frequency |
Hz |
50 |
||||
3 |
Main bus rated current |
A |
1250/1600/2000/2500 |
||||
4 |
Main bus rated current |
A |
630/1250/1600 |
||||
5 |
Rated insulation level |
Lightning impulse withstand voltage (peak) |
kV |
185 |
215 |
||
1min power frequency withstand voltage (valid) |
kV |
Phase to phase and phase to ground |
Disconnector fractures |
||||
95 |
115 |
||||||
6 |
Rated short-circuit open current |
kA |
25 |
31.5 |
|||
7 |
Rated short-circuit closing current (peak) |
kA |
63 |
80 |
|||
8 |
Rated short-time withstand current (4 s) |
kA |
25 |
31.5 |
|||
9 |
Rated peak withstand current |
kA |
63 |
80 |
|||
10 |
Related voltage of supplementary controlled return loop |
V |
~110/-110;~220/-220 |
||||
11 |
IP Grade |
Enclosure IP4X IP2X when the door of the chamber and circuit breaker chamber is opened |