+86-0431-84158222
+86-0431-84155885
S/N |
Item |
Unit |
Parmeters |
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
rated power-frequency withstand voltage (1min) (phase-to-ground, phase-to-phase and phase-to-fracture) |
kV |
42/48 |
4 |
Rated lightning impulse withstand voltage (peak) (phase-to-ground, phase-to-phase and phase-to-fracture) |
kV |
95 |
5 |
Rated current |
A |
630/1250/1600/2000、2500/3150 /4000 |
6 |
Rated short-circuit open current |
kA |
25/31.5/40/50 |
7 |
Rated short-time withstand current (4 s) |
kA |
25/31.5/40/50 |
8 |
Rated short-circuit closing current (peak) |
kA |
63/80/100/125 |
9 |
Rated peak withstand current |
kA |
63/80/100/125 |
10 |
Rated short circuit current breaking times |
times |
30 |
11 |
Rated operation sequence |
O-0.3s-CO-180s-CO |
|
12 |
Closing / opening time |
ms |
≤70/≤50 |
13 |
Rated operating voltage |
V |
AC110/220 DC110/220 |
14 |
Mechanical life |
times |
30000/20000 |
This vacuum terminal post uses advanced automatic pressure gelatin process (APG) to directly seal small ultra-low resistance vacuum arc extinguishing chamber and other parts of the main circuit in epoxy resin, which simplify the assembly process of terminal post, prevent any loosening caused by vibration of connecting bolts of conductor circuit in the vacuum arc extinguishing chamber due to movement, thus improving reliability. The surface of the vacuum arc extinguishing chamber is not affected by external mechanical force and external environment, which further improving electric field distribution on the terminal post.