+86-0431-84158222
+86-0431-84155885
S/N |
Rated parameters |
Unit |
Parameters |
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50/60 |
3 |
Rated current |
A |
630 |
4 |
Rated short-time withstand current |
kA |
20 |
5 |
Rated peak withstand current |
kA |
50 |
6 |
Rated duration of short-circuit |
s |
4 |
7 |
Rated short-circuit open current |
kA |
20 |
8 |
Rated short-circuit closing current (peak) |
kA |
50 |
9 |
Rated operation sequence |
O-0.3s-CO-180s-CO |
|
10 |
Rated active load breaking current |
A |
630 |
11 |
Power frequency voltage (1min) (phase-to-ground, phase-to-phase and phase-to-fracture) |
kV |
42/48 (dry type), 34(wet type) |
12 |
Rated line-charging breaking current |
A |
10 |
13 |
Rated short circuit current breaking times |
Time |
30 |
14 |
Mechanical life |
Time |
10000 |
15 |
Resistance of contact circuit of each phase |
μΩ |
cable output ≤600, bushing output ≤200 |
16 |
Clearance between open contacts |
mm |
8±1 |
17 |
Over-travel of the contact |
mm |
2.5~4 |
18 |
Contact closing bounce time |
ms |
≤10 |
19 |
Clearance between isolating fractures |
mm |
25~30 |
20 |
Overtravel of isolating fracture |
mm |
1.2±0.2 |
21 |
Three-phase closing/opening non-synchronism |
ms |
≤3 |
22 |
Opening time |
ms |
<300 |
23 |
Sulfur hexafluoride gas rated pressure |
MPa |
“0” |
24 |
Enclosure protection class |
IP67 |
1. Vacuum arc extinguish, SF6 gas insulation, excellent breaking performance.