+86-0431-84158222
+86-0431-84155885
S/N |
Item |
Unit |
Parameters |
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
Rated current |
A |
630 |
4 |
Rated short-time withstand current |
kA |
20 |
5 |
Rated peak withstand current |
kA |
50 |
6 |
Rated duration of short-circuit |
s |
4 |
7 |
Rated short-circuit open current |
kA |
20 |
8 |
Rated short-circuit closing current (peak) |
kA |
50 |
9 |
Rated operation sequence |
O-0.3s-CO-180s-CO |
|
10 |
Rated active load breaking current |
A |
630 |
11 |
Dc component of rated short-circuit breaking current |
≮40% |
|
11 |
Rated short-time power frequency voltage (1min) withstand voltage (phase-to-ground, phase-to-phase and phase-to-fracture) |
kV |
42 |
12 |
Rated lightning impulse withstand voltage (peak) phase-to-ground, phase-to-phase and phase-to-vacuum fracture) |
kV |
75 |
13 |
auxiliary circuit 1min power frequency withstand voltage |
kV |
2 |
Earth fault breaking current between different phase |
kA |
||
14 |
Rated line-charging breaking current |
A |
10 |
15 |
Rated short circuit current breaking times |
Time |
30 |
16 |
Mechanical life |
Time |
10000 |
18 |
Clearance between open contacts |
mm |
9±1 |
19 |
Over-travel of the contact |
mm |
2.5~4 |
20 |
Contact closing bounce time |
ms |
≤2 |
23 |
Three-phase closing/opening non-synchronism |
ms |
≤3 |
24 |
Opening speed |
m/s |
1.2±0.2 |
25 |
Closing speed |
m/s |
0.6+0.2 |
26 |
Insulating medium |
Re-closing and air insulation |
|
Weight (without isolation) |
kg |
74 |
1. This product adopts integrated structure design and the three-phase posts linked with electrical part and operating structural box respectively to form a unified whole, stable and reliable breaking performance, free of combustion and explosion hazard, maintenance-free, small in size, light weight and long service life.